Optimized for Aerial- and Duct Installation with fiber counts up to 96 fibers
All-Dielectric, Self Supporting (ADSS) Aerial Loose Tube Fiber Optic Cable Dry core design PowerGuide® SkyLight
All-Dielectric, Self Supporting (ADSS) Aerial Loose Tube Fiber Optic Cable Dry core design PowerGuide® SkyLight
Optimized for Aerial- and Duct Installation with fiber counts up to 96 fibers
Version illustrated is the 96 Fiber 8 Element Cable
Product Specification | |||||
---|---|---|---|---|---|
Fiber Count | Tubes | Core Design | Outer Diameter [mm] | Cable Weight [kg/km] | AT-Code** |
84 | 7 (12F) | 1+8 (1 Filler*) | 11.9 | 120 | AT-[][][]17UT-084-CMEA |
96 | 8 (12F) | 1+8 | 11.9 | 120 | AT-[][][]17UT-096-CMEA |
This table shows nominal diameter and weight values which may differ in shipments. *Fillers are natural colored. **Please refer to the LIGHTERA AT- Code. The blanks specify the fiber type. |
Identification Tube and Fiber Color Code | |
---|---|
1 | Blue |
2 | Orange |
3 | Green |
4 | Brown |
5 | Grey |
6 | White |
7 | Red |
8 | Black |
9 | Yellow |
10 | Violet |
11 | Pink |
12 | Aqua |
Note | Alternative tube and fiber color code available on request. |
Sheath Marking |
---|
Lightera OPTICAL ADSS CABLE [ID] [MM/YYYY] [Handset Sign] xxxF [Meter Marking] Alternative sheath printing available on request. In case of order the exact sheath printing text will be clarified with the customer. |
Shipping Information | |||
---|---|---|---|
Cable Length | Drum Diameter | Drum Width | Shipping Weight (calc.) Cable + Drum |
2 Km | 1200 mm | 780 mm | 310 kg |
4 Km | 1400 mm | 780 mm | 570 kg |
6 Km | 1550 mm | 1060 mm | 850 kg |
8 Km | 1700 mm | 1060 mm | 1130 kg |
The shipping information are given for one-way reels. Reusable reels are available on request. |
Temperatures (IEC 60794-1-22-F1) | |
---|---|
Operation | -40°C to +70°C |
Installation | -15°C to +60°C |
Storage/shipping | -40°C to +70°C |
Standard | IEC 60794-1-22-F1 |
Sag and Tension Calculation AT-[ ][ ][ ]17UT-xxx-CMEA | |||
---|---|---|---|
Conditions | NESC Light Loading | NESC Medium Loading | NESC Heavy Loading |
Ice Thickness | 0 mm | 6.4 mm | 12.7 mm |
Wind Pressure | 431 N/m² (95.5 km/h) | 192 N/m² (63.6 km/h) | 192 N/m² (63.6 km/h) |
Low Temperature | -1 °C | -9.4 °C | -17.8 °C |
Safety Factor | 0.73 N/m | 2.92 N/m | 4.38 N/m |
Tension @ Maximum Span for 1,0 % Installation Sag |
|||
Maximum Span | 150 m | 100 m | 60 m |
MRCL (Maximum Rated Cable Load) | 4000 N | 4000 N | 4000 N |
MIT (Maximum Installation Tension) | 2100 N | 1400 N | 850 N |
Installation Temperature | 23 °C | 23 °C | 23 °C |
Cable Modulus | 798.2 kg/mm² | 798.2 kg/mm² | 798.2 kg/mm² |
CTE (C-1) | 1.67E- 05 | 1.67E- 05 | 1.67E- 05 |
|
---|
PLP: | |
Dead End Assembly: |
FIBERLIGN® Dielectric Dead-end for ADSS, 2872003C1E1, Max. Tension: 2500 lbs. (1135 kg) |
Fixed Tangent Support: |
FIBERLIGN® Aluminum Support for ADSS, 4450099 |
Suspended Support: |
FIBERLIGN® Aluminum Suspension for ADSS, 4450199 |
Slack Storage Devices: |
FIBERLIGN® In-Span Storage System, FIS12A |
Down Lead Cushion: |
FIBERLIGN® Downlead Cushion for ADSS, 8003041 |
Vibration Dampers: |
FIBERLIGN® Dielectric Damper for ADSS Cable, 50502272 |
Telenco: |
|
Dead End Assembly: |
TELENCO® GSDE AR Helical dead-ends with armor rods, Model GSDE AR 1150 (PN 7641) |
Vibration Dampers: |
TELENCO® Vibration damper VIB, Model VIB117 (PN 09140) |
Suspension Support: |
TELENCO® DSAL Mobile suspension clamp, Model DSAL1150 (PN 09568) |